A leak location test needs to
be conducted if the line acceptance test fails. The leak
location test procedure is as follows:
1. String pipe
using Cherne's Air-Loc Line Stringer or other method, attaching
winch cable which is then pulled back through line.
2.
Attach two pipe plugs connected together with interconnect hose
to winch cable and place in pipeline. |
3. Connect 500' triple hose to front plug.
4. Conduct pressure test on first 22' segment of sewer line
and record results.
5. Advance plugs forward 22' using
the winch and conduct test, once again recording results. Repeat
procedure until entire line has been tested.
|