"Your Construction Partner"
   Since 1970
 


800-877-1426 
CORPORATE
800-877-4571ICM ONLINE STORE

 

 

HOME PAGE   SITE MAP CONTACT US   BRANCH  LOCATIONS

ABOUT ICM

ICM News Page
Used Equipment
Email ICM
Construction Info
 & Link Page
Employment

We Accept

Financing is available with low monthly payments!!!! Contact your sales rep for details.

 

 

 RICE HYDROSTATIC PNEUMATIC TEST PUMP INSTRUCTIONS

BACK


Rice Hydrostatic Pneumatic Test Pump

 QUICK REFERENCE OPERATING INSTRUCTIONS

REQUIRED EQUIPMENT

  1. One air compressor (100 PSI, 100 SCFM or 135 SCFM): This equipment will operate from 100 SCFM to 135 SCFM. Do not exceed 135 SCFM.

CONNECTING THE PUMP

  1. Position the HP-1 Rice Hydrostatic Test Pump within six feet of the line to be tested. This allows two feet for hose adjustments.

  2. Connect the 3/4" water supply hose to the 3/4" hose swivel located on lower left front side of unit. Please secure tight.

  3. Connect the airline from the compressor to the air filter located on backside of the unit. NOTE: BE SURE THE FILTER IS DRAINED OF ANY WATER OR DIRT PARTICLES BEFORE AND AFTER USE. TO DO THIS, USE THE MANUAL DRAIN VALVE LOCATED ON THE BOTTOM OF THE FILTER. Secure the twist lock with the safety pin. Leave ball valve on compressor closed.

  4. Secure the 8' high pressure outlet hose to the lower RIGHT side of the unit. PLEASE SECURE TIGHTLY. This is the 10,000 PSI outlet side.

  5. CONNECT THE OUTLET HOSE TO THE LINE TO BE TESTED.

OPERATING THE PUMP

  1. Be sure the ball valve on the front of the unit is in the closed position. This is a safety device that allows you to control water pressure to the best line.

  2. Turn on the water.

  3. Open the bleeder valve on the test line to bleed off excess air. NOTE: this should be done several times during the test cycle.

  4. Start the compressor.

  5. Once the compressor has reached operating temperature, open the valve slowly to allow air to flow to the Rice Hydrostatic Test Pump.

  6. At the unit, adjust the air regulator (yellow knob in the middle of the unit) by pulling out the locknut and turning clockwise to increase pressure or counter-clockwise to decrease pressure. NOTE: THE PUMP IS PRE-SET AT THE FACTORY TO 80 PSI AT 100SCFM AND OUTPUT PRESSURE OF 8800 PSI.

  7. The enclosed chart will give you PSI settings for different output pressures;

    Air PSI Output pressure
    20 2000
    30 3400
    40 4500
    50 5600
    60 6800
    70 7800
    80 8800
    90 & 100 10000
  8. Set the air pressure to 100 PSI. This will give maximum operating pressure at 10,000 PSI.

  9. Open ball valve slowly and watch the pressure gauge until desired pressure is reached. Once acceptable pressure is reached, close ball valve and monitor the gauge for any pressure drop. If the pressure is dropping, check the following three things:
    bullet

    Output hose connection at pump

    bullet

    Output hose connection at test line

    bullet

    Leaking test line or air in the test environment

  10. If the pressure gauge remains constant, turn off compressor and monitor gauge for your prescribed test time. When test is complete, open the high pressure bleeder valve located in the center of the unit. Bleed off the water pressure. Repeat the above steps for multiple lines. Be sure the air pressure gauge reads zero before disconnecting the air line from pump. To release pressure faster, open the ball valve on the front of the unit.

REMEMBER THESE CAUTIONS

  1. Please be assured that all hoses from the compressor to the HP-1 have been certified to operate in the 100 to 135 SCFM range.

  2. Prior to testing any high pressure test line, check all connections, hoses, and fittings to assure that they are properly tightened.

  3. *** In this range of 10,000 PSI, use extreme caution in testing of lines***.

May 07, 2012 Copyright © 2001 ICM Ebiz Division.  ebiz@icminc.us